- Phase/harmonic components [RMS amperes, phasor angle degrees]
- [[10,0],[10,120],[10,240],[3,0],[3,0],[3,0]]
- Modeled neutral current (A)
- 9
- Real phasor sum (A)
- 9
- Imaginary phasor sum (A)
- 0
Try another scenario
- Phase/harmonic components [RMS amperes, phasor angle degrees]
- [[11,0],[10,120],[10,240],[3,0],[3,0],[3,0]]
- Modeled neutral current (A)
- 10
- Real phasor sum (A)
- 10
- Imaginary phasor sum (A)
- 0
Calculation method
Calculation method
Modeled neutral current (A)
Phasor sum of supplied same-frequency components; separate harmonic orders must be evaluated separately.
Real phasor sum (A)
Phasor sum of supplied same-frequency components; separate harmonic orders must be evaluated separately.
Imaginary phasor sum (A)
Phasor sum of supplied same-frequency components; separate harmonic orders must be evaluated separately.
Symbols and units
- a
- Phase/harmonic components [RMS amperes, phasor angle degrees]
Use the units shown. A list keeps the order in which you enter its values. The symbol ^ means “raised to the power of”.
Assumptions & limits
Assumptions & limits
- One frequency at a time; phase angles are supplied explicitly. Do not add different harmonic frequencies as same-frequency phasors. Supported limits: Finite numeric values bounded to 1e9 magnitude; lists and tables contain 1–100 records unless a stricter bound is stated. Inputs use the units shown. Lists explicitly paired by a method must have matching lengths; independent polynomial coefficient vectors may differ. Respect stated physical, interpolation, policy and computational domain limits.
Are these inputs private?
These calculations run in your browser. A shared link contains the values you choose to share. Only questions submitted to the separate AI finder are sent to OpenAI.