Examples
Examples
Try the starting example
- Water flow (m³/s)
- 0.005
- Pipe length (m)
- 100
- Inside diameter (m)
- 0.1
- Hazen–Williams C
- 120
- Empirical water head loss (m)
- 0.611524
Try another scenario
- Water flow (m³/s)
- 0.0055000000000000005
- Pipe length (m)
- 100
- Inside diameter (m)
- 0.1
- Hazen–Williams C
- 120
- Empirical water head loss (m)
- 0.729579
Calculation method
Calculation method
Empirical water head loss (m)
SI Hazen–Williams h=10.67 L Q^1.852/(C^1.852 D^4.8704).
Symbols and units
- a
- Water flow (m³/s)
- b
- Pipe length (m)
- c
- Inside diameter (m)
- d
- Hazen–Williams C
Use the units shown. A list keeps the order in which you enter its values. The symbol ^ means “raised to the power of”.
Assumptions & limits
Assumptions & limits
- Empirical water formula; no nonwater fluids, temperature correction or fire-system compliance. Supported limits: All required fields must be finite values of the exact declared type and within displayed bounds. Lists contain1–1000 finite numbers. JSON tables are numeric rectangular rows, at most100 rows and30 columns; individual tools have stricter shape/domain constraints. Empirical water formula; no nonwater fluids, temperature correction or fire-system compliance.
Are these inputs private?
These calculations run in your browser. A shared link contains the values you choose to share. Only questions submitted to the separate AI finder are sent to OpenAI.
Further reading
Background reading; this does not imply endorsement or independent review of SumFizz.