Heat exchanger effectiveness calculator

Calculate hot-side heat duty and cold-side heat duty with your own figures.

Your numbers

Use the units shown. Results update as you change valid inputs.

Use hot-side heat duty and cold-side heat duty to compare changes to your inputs. The method and limits below explain the scope.

Examples

Examples

Try the starting example

Hot stream heat capacity rate (W/K)
1000
Cold stream heat capacity rate (W/K)
800
Hot inlet temperature (°C)
80
Cold inlet temperature (°C)
20
Hot outlet temperature (°C)
50
Cold outlet temperature (°C)
57.5
Hot-side heat duty (W)
30000
Cold-side heat duty (W)
30000
Capacity rate ratio
0.8
Hot-side effectiveness fraction
0.625
Energy-balance mismatch (W)
0

Try another scenario

Hot stream heat capacity rate (W/K)
1100
Cold stream heat capacity rate (W/K)
800
Hot inlet temperature (°C)
80
Cold inlet temperature (°C)
20
Hot outlet temperature (°C)
50
Cold outlet temperature (°C)
57.5
Hot-side heat duty (W)
33000
Cold-side heat duty (W)
30000
Capacity rate ratio
0.727273
Hot-side effectiveness fraction
0.6875
Energy-balance mismatch (W)
3000
Calculation method

Calculation method

Hot-side heat duty (W)

Qh=Ch(Thi-Tho), Qc=Cc(Tco-Tci); Cr=Cmin/Cmax; effectiveness=Qh/[Cmin(Thi-Tci)].

Cold-side heat duty (W)

Qh=Ch(Thi-Tho), Qc=Cc(Tco-Tci); Cr=Cmin/Cmax; effectiveness=Qh/[Cmin(Thi-Tci)].

Capacity rate ratio

Qh=Ch(Thi-Tho), Qc=Cc(Tco-Tci); Cr=Cmin/Cmax; effectiveness=Qh/[Cmin(Thi-Tci)].

Hot-side effectiveness fraction

Qh=Ch(Thi-Tho), Qc=Cc(Tco-Tci); Cr=Cmin/Cmax; effectiveness=Qh/[Cmin(Thi-Tci)].

Energy-balance mismatch (W)

Qh=Ch(Thi-Tho), Qc=Cc(Tco-Tci); Cr=Cmin/Cmax; effectiveness=Qh/[Cmin(Thi-Tci)].

Symbols and units
a
Hot stream heat capacity rate (W/K)
b
Cold stream heat capacity rate (W/K)
c
Hot inlet temperature (°C)
d
Cold inlet temperature (°C)
e
Hot outlet temperature (°C)
f
Cold outlet temperature (°C)

Use the units shown. A list keeps the order in which you enter its values. The symbol ^ means “raised to the power of”.

Assumptions & limits

Assumptions & limits

  • Measured steady sensible-heat streams, constant heat capacity; no NTU geometry or phase-change model. Supported limits: All required fields must be finite values of the exact declared type and within displayed bounds. Lists contain1–1000 finite numbers. JSON tables are numeric rectangular rows, at most100 rows and30 columns; individual tools have stricter shape/domain constraints. Measured steady sensible-heat streams, constant heat capacity; no NTU geometry or phase-change model.
Are these inputs private?

These calculations run in your browser. A shared link contains the values you choose to share. Only questions submitted to the separate AI finder are sent to OpenAI.