Examples
Examples
Try the starting example
- Air mass flow (kg dry air/s)
- 1.5
- Inlet humidity ratio (kg/kg)
- 0.012
- Outlet humidity ratio (kg/kg)
- 0.008
- Operating duration (hours)
- 8
- Condensate flow (kg/hour)
- 21.6
- Collected condensate (kg)
- 172.8
Try another scenario
- Air mass flow (kg dry air/s)
- 2.5
- Inlet humidity ratio (kg/kg)
- 0.012
- Outlet humidity ratio (kg/kg)
- 0.008
- Operating duration (hours)
- 8
- Condensate flow (kg/hour)
- 36
- Collected condensate (kg)
- 288
Calculation method
Calculation method
Condensate flow (kg/hour)
Dry-air mass flow × humidity-ratio reduction; kg water approximately litres only if density is assumed separately.
Collected condensate (kg)
Dry-air mass flow × humidity-ratio reduction; kg water approximately litres only if density is assumed separately.
Symbols and units
- a
- Air mass flow (kg dry air/s)
- b
- Inlet humidity ratio (kg/kg)
- c
- Outlet humidity ratio (kg/kg)
- d
- Operating duration (hours)
Use the units shown. A list keeps the order in which you enter its values. The symbol ^ means “raised to the power of”.
Assumptions & limits
Assumptions & limits
- User-supplied measurements and assumptions; Dry-air mass flow × humidity-ratio reduction; kg water approximately litres only if density is assumed separately. Supported limits: Finite numeric values bounded to 1e9 magnitude; lists and tables contain 1–100 records unless a stricter bound is stated. Inputs use the units shown. Lists explicitly paired by a method must have matching lengths; independent polynomial coefficient vectors may differ. Respect stated physical, interpolation, policy and computational domain limits.
Are these inputs private?
These calculations run in your browser. A shared link contains the values you choose to share. Only questions submitted to the separate AI finder are sent to OpenAI.